HP | 200 Volts | 440-480 Volts |
---|---|---|
125 | 359 | 156 |
150 | 414 | 180 |
200 | 552 | 240 |
250 | – | 302 |
How do I convert HP to amps?
Convert to Amps
- Amps = 1 HP × 746 W120 V × .9.
- Amps = 746120 V × .9.
- Amps = 746108.
How many HP is 15 amps?
At 100% efficiency, the most a 15-amp, 120v outlet in a home circuit can supply is 15 x 120 or 1800w; 1800 divided by 746 equals 2.41 hp.
How many amps does a 300 hp motor draw?
Here are the Full Load Amp (FLA) values for typical 230VAC and 480VAC 3 phase motors.
Motor horsepower | Full load amps 230VAC | Full load amps 460VAC |
---|---|---|
150 | 360 | 180 |
200 | 480 | 240 |
250 | 580 | 290 |
300 | 696 | 348 |
What size breaker do I need for a 200 hp motor?
So, assuming an inverse time breaker, the 200 hp motor would have a maximum branch circuit OCPD of 240 amps x 250% = 600 amp.
What size breaker do I need for a 40 hp motor?
Full-Load Current and Circuit Protection Data for Three-Phase AC Motors
Motor Horsepower | Breaker Size | |
---|---|---|
20 | 230 V 460 V | 100 50 |
25 | 230 V 460 V | 100 50 |
30 | 230 V 460 V | 125 70 |
40 | 230 V 460 V | 175 100 |
How many amps is a 40 hp motor?
AC Motor Full Load Amperes
HP | 200 Volts | 550-600 Volts |
---|---|---|
25 | 78.2 | 27 |
30 | 92 | 32 |
40 | 120 | 41 |
50 | 150 | 52 |
What size breaker do I need for a 10 hp motor?
Full Load Current: Three Phase AC Motors
Motor Horsepower | Size Breaker | |
---|---|---|
5 | 230V 460V | 15 15 |
7-1/2 | 230V 460V | 40 30 |
10 | 230V 460V | 50 30 |
15 | 230V 460V | 70 40 |
How many HP is 8 amps?
Common Amps to Horsepower Conversions
Amps | Horsepower | Efficiency |
---|---|---|
7 A | 1.01 HP | 90% |
8 A | 1.16 HP | 90% |
9 A | 1.3 HP | 90% |
10 A | 1.45 HP | 90% |
How many amps is a 5 hp motor?
AMP DRAW BASED ON HORSEPOWER
HP | 1 Phase Amps | 3 Phase Amps |
---|---|---|
115 volt | 208 volt | |
5 | 56 | 16.7 |
7-1/2 | 80 | 24.2 |
10 | 100 | 30.8 |
What size breaker do I need for a 3 HP motor?
What size breaker do I need for a 3 HP motor? A 20 amp breaker is all you’d ever need for a 220v 3HP motor. It wouldn’t hurt anything to run 30amp circuits if you so choose, but it’s overkill.
How much current would a 1.5 HP 240v motor draw?
The 1.5 HP Baldor motor that turns at 1725 will draw 18 amps according to its name plate.
What size breaker do I need for a 1 hp motor?
How to Calculate How What Size Circuit Breaker a Machine will Need:
HorsePower of Main Motor | 220 Volts, 1 phase | 220 Volts, 3 phase |
---|---|---|
1 Hp | 5.6 Amps | 2.8 |
2 | 11.2 | 5.6 |
3 | 16.8 | 8.4 |
4 | 22.4 | 11.2 |
What size breaker do I need for a 15 amp motor?
A 12 wire and a 20A breaker is needed. 15A ends can be used on 20A circuits.